Detcon FP-624D Manual do Utilizador Página 14

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 13
Model FP-624D
FP-624D Instruction Manual Rev. 1.2 Page 10 of 42
and 24VDC source is shown in the Table below. The maximum wire size for termination in the Junction Box
is 14 AWG.
Table 1 Wire Gauge vs. Distance
AWG Wire Dia. Meters Feet
Over
-
Current
Protection
22
0.723mm
700
2080
3A
20
0.812mm
1120
3350
5A
18
1.024mm
1750
5250
7A
16
1.291mm
2800
8400
10A
14
1.628mm
4480
13,440
20A
NOTE 1:
Wiring table is based on stranded tinned copper wire and is designed to serve as a
reference only.
NOTE 2:
Shielded cable is required for installations where cable trays or conduit runs include
high voltage lines or other possible sources of induced interference. Separate conduit runs are
highly recommended in these cases.
NOTE 3:
The supply of power shou
ld be from an isolated source with over
-
current protection
as stipulated in Table 1 Wire Gauge vs. Distance.
NOTE 4:
A 250 ohm load resistor is need
ed on the 4
-
20 mA line when it is not being used.
Terminal Connections
CAUTION: Do not apply System power to the sensor until all wiring is properly terminated. Refer
to Section 2.8 Initial Start Up
Figure 11 Sensor Connector PCB
a) Remove the junction box cover and unplug the Transmitter Module. Identify the terminal blocks for
customer wire connections.
Customer
Wiring
White
Blue
Yellow
Black
Wiring to
LEL Sensor
Power (+ -)
4-20 mA
RS-485 (A,B)
Fault
Alarm 2
Alarm 1
Vista de página 13
1 2 ... 9 10 11 12 13 14 15 16 17 18 19 ... 45 46

Comentários a estes Manuais

Sem comentários