1600A-N1R
1600A-N1R Instruction Manual Rev. 0.1 Page 19 of 38
Figure 27 Model DI-4 Module
4.1.6 4-20mA Output Setup
This menu entry is used to address Detcon AO-4 modules 4-20mA output.
NOTE: If there are no AO-4 modules being used, do not enter any device and address information on this
screen. Misinformation entered here will cause the controller to generate a ‘No Communication Fault’.
Figure 28 Set-up 4-20mA Outputs
For example, assume setting up two AO-4 modules. Make sure to set each AO-4 module to a unique ID#
using the front panel switches. If Device #s 1 through 4 are already being used for DA-4 and RL-4 modules,
then set these two AO-4 modules to 5 and 6. The entered values should then look like this:
CH# AO4 Address
01 thru 04 81 Hex
05 thru 08 85 Hex
09 thru 12 89 Hex
13 thru 16 8D Hex